- Title
- Permitted Gaps in Corridor Doors and Doors in Smoke Barriers
- Memo #
- 07-18
- Posting Date
- 04/20/2007
- Fiscal Year
- 2007
- Summary
- In a smoke compartment that is not fully sprinklered, a gap between the face of a corridor door and the door stop should not exceed 1/4-inch, provided that the door latch mechanism is functioning. In a smoke compartment that is fully sprinklered, a gap between the face of a corridor door and the door stop should not exceed 1/2-inch, provided that the door latch mechanism is functioning.